Current Transducer HTFS 200..800-P/SP2
IPN = 200 - 400 - 800A
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
All Data are given with a R L = 10 kΩ
Electrical data
Primary nominal
current rms
IPN (A)
Primary current
measuring range
IPM (A)
200
400
800
VOUT
VREF
RL
ROUT
CL
VC
IC
± 300
± 600
± 1200
Type
RoHS since
date code
Features
HTFS 200-P/SP2
HTFS 400-P/SP2
HTFS 800-P/SP2
Output voltage (Analog) @ IP
IP = 0
Reference voltage 1) - Output voltage
VREF Output impedance
VREF Load impedance
Load resistance
Output internal resistance
Capacitive loading < 1
Supply voltage (± 5 %)
Current consumption @ VC = 5 V
45326
45060
45060
VREF ±(1.25·IP/IPN) V
VREF ± 0.025
V
1/2VC ± 0.025
V
typ. 200
Ω
≥ 200
kΩ
≥2
kΩ
< 10
Ω
µF
5
V
22
mA
εL
TCVOE
TCVREF
TCVOUT /VREF
TCVOUT
VOM
t ra
tr
di/dt
Vno
BW
Accuracy 2) @ IPN , TA = 25°C
Linearity error 0 .. 1.5 x IPN
Temperature coefficient of VOE @ IP = 0
Temperature coefficient of VREF
Temperature coefficient of VOUT / VREF @ IP = 0
Temperature coefficient of VOUT
Magnetic offset voltage @ IP = 0,
after an overload of 3 x IPN DC
Reaction time @ 10 % of IPN
Response time to 90 % of IPN step
di/dt accurately followed
Output voltage noise (DC ..10 kHz)
(DC .. 1 MHz)
Frequency bandwidth (-3 dB) 3)
≤±
≤±
≤±
≤±
≤±
1
0.5
0.3
0.01
0.2
% of IPN
% of IPN
mV/K
%/K
mV/K
Ambient operating temperature
Ambient storage temperature
Mass
Standards
according to UL 94-V0
Advantages
ratings range
• High immunity to external
interference.
• VREF. IN/OUT
≤ ± 0.05% of reading/K
Applications
< ± 0.5
1
4
>4
>4
> 220
kV
kV
kV
mm
mm
If insulated cable is used for the primary circuit, the
voltage category could be improved with the following table :
Cable insulation (primary)
Category
HAR 03
300V CAT III
HAR 05
400V CAT III
HAR 07
500V CAT III
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the following
manufacturer's operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
070827/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HTFS 200..800-P/SP2 (in mm. 1 mm = 0.0394 inch)
Ip
40
0.5
16.5
33
R3
20.3
3
33
d22
26
16
5
3-P=2.54
4
1
4-d=1.0
4.5
3.5+/-1
4-0.25x0.5
7
Required Connection Circuit
Terminal Pin
HTFS
4 Vref(IN/OUT)
3
2 0V
1
Vref(IN/OUT)
Output
Output
+5V
47nF
4.7nF
1...+5V
2...0V
3...Output
4...Vref(IN/OUT)
0V
+5V
47nF
Operation Principle
+Vc
Vout
Vref.(IN/OUT)
0V
Ip
Remarks
Mechanical characteristics
•
•
•
•
General tolerance
Fixation
Recommended PCB hole
Fastening & connection of secondary
Recommended PCB hole
± 0.2 mm
4 pins x Ø 1.0
Ø 1.2 mm
4 pins 0.5 x 0.25
Ø 0.7 mm
• VOUT is positive when IP flows in the direction of the arrow.
• Temperature of the primary conductor should not exceed
120°C.
Page 3/3
070827/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
很抱歉,暂时无法提供与“HTFS 200-P/SP2”相匹配的价格&库存,您可以联系我们找货